CTI 2500-ADP1 Analogue Wiring Adapter

2500-ADP1 Analogue Wiring Adapter for Series 500

Description of the 2500-ADP1

The 2500-ADP1 is a wiring adapter that converts 500 Series analogue field www.ge-drive.com wiring from the basic format to the 40-pin connector used on CTI 2500 SeriesTM analogue input/output modules.

The 2500-ADP1 is a wiring adapter that converts the analogue field wiring of the 500 Series from the basic format to the 40-pin connector used on CTI 2500 SeriesTM analogue I/O modules.

Converts analogue field wiring from basic format to the 40-pin connector used on the CTI 2500 SeriesTM analogue I/O modules.

This allows for quick upgrades of existing 500 Series systems to the newer, more suitable 2500 SeriesTM.

Features

The 2500-ADP1 cable allows for the following conversions

field wiring:

– 500-5037A 8-channel analogue input connector to CTI 2558 8-channel analogue input 40F connector.

– 500-5047A 8-channel analogue output connector to CTI 2562 8-channel analogue output 40F connector.

Instructions

Method A – Installing a New Module into an Existing 500 Series I/O Adapter

Chassis

1. Disconnect power to the Series 500 chassis

2. Remove the 500-5037A/47A to be upgraded.

3. Install the 2500-IADP into the slot where the 500 module was removed.

4. Configure the 2558/2562 to match the 500 module to be replaced .

5. Install the 2558/2562 into the 2500-IADP .

6. Connect the edge card connector of the 2500-ADP1 to the existing 5037A / 5047A field wiring connector.

(The screen label on the 2500-ADP1 indicates a 5037A / 5047A field wiring connector).

Connect the edge card connector of the 2500-ADP1 to the existing 5037A / 5047A field wiring connector.

(The screen label on the edge card connector shows pin 1 and pin A.)

7. Remove any 250 ohm resistors that may be installed in the 5037A / 5047A field wiring connector. 2558 / 2562 do not require these resistors.

8. Connect the 40F connector to the 2558/2562.

9. Restore power to the rack.

Method B – Installing a New Module into a New 2500 SeriesTM Base

1. Disconnect power to the 500 Series chassis.

2. Remove the 500-5037A/47A to be upgraded.

3. Configure the 2558/2562 to match the 500 module to be replaced.

4. Install the 2558/2562 into the 2500 SeriesTM base.

5. Connect the edge card connector of the 2500-ADP1 to the existing 5037A / 5047A field wiring connector (The screen label on the edge card connector shows pin 1 and pin A.)

6. remove any 250 ohm resistors that may be installed in the 5037A / 5047A field wiring connector. 2558 / 2562 do not require these resistors.

7. Connect the 40F connector to the 2558 / 2562.

8. Restore power to the rack.

CTI 2559-RTD 8-Channel RTD Input Module

DESCRIPTION

The 2559-RTD is a high-speed 8-channel RTD input module designed for compatibility with the SIMATIC® 505 I/O base.

The Model 2559-RTD converts RTD input signals to Product Bulletin proportional temperature values.

Features

SIMATIC® 505 basic format

1500V channel to PLC backplane isolation

Fast 2 ms update time per channel

Detects open circuits in RTD or field wiring

Compensates for wire resistance

Supports 0 – 100 mV input on any channel

Specification

Input Channels: 8 independently configurable www.ge-drive.com RTD input channels

RTD Type: 100 Ω Platinum: (TCR = 0.003850. Ω/Ω/oC) (European DIN43760 standard)

Temperature range: -198oC to 849.8oC (-327.6oF to 1561.6oF)

120Ω Nickel: (TCR = 0.00672. Ω/Ω/oC)

Temperature Range: -79.8oC to 260.0oC (-111.6oF to 500.0oF)

(Other RTD types on special request) 10Ω Copper

Absolute temperature accuracy: +0.4oC (+0.8oF)

Millivolt Range: 0 to 103.04 millivolts

Millivolt Input Impedance: >10KΩ @ 60Hz >10KΩ @ 60Hz >1000MΩ @ DC

Absolute millivolt accuracy +0.5% full scale or +500µV

Wire Compensation: 20Ω per wire

RTD probe bias current: 250 µA (nominal)

Digital filter time constant: 0.3 seconds

Output Units: Celsius or Fahrenheit (all outputs are jumper selectable)

Repeatability: 0.05% full scale

Resolution: 0.025% full scale

Update Time: 2 milliseconds per channel

Common mode rejection >110db @ 60Hz (digital filtering disabled)

Normal mode rejection >145db @ 60Hz (digital filter enabled)

Input Protection

Input ESD protection: 20.000V

Over-range protection: 20 VDC input to common

Isolated 1500 VDC channel to PLC

Standard shipping configuration:

3-wire 100Ω platinum

Digital filtering enabled

Celsius

Connectors: Fixed 32-position terminal strip labeled 1-32 from top to bottom

Wire Gauge: 18-24 AWG 18-24 AWG

Backplane Power: 2.75W @ 5 VDC

Module Size Single Wide

Operating Temperature 0o to 60oC (32o to 140oF)

Storage Temperature: -40o to 85oC (-40o to 185oF)

Relative Humidity: 5% to 95% (non-condensing)

Agency approvals pending: UL, ULC, CE FM (Class 1 Division 2)

Shipping Weight: 1.5 lbs (0.68 kg)

Related Product Recommendations:

IC660TBD024K GeniusI/O Terminal Assembly Module

HE697RTM700B High-Speed Counter Module

1769-OF8C Analog Output Module

D1961SH45T Rectifier Diode Industrial Robot Accessories

1769-OF8C Analog Output Module

1769-PB4 Power Supply Module

BSFC-01C Charge control board SP kit gate driver board

1769-OF2 Analog Output Module

1B30035H01 Process Control Base

5X00419G01 Ethernet Link controller

Search for products

Back to Top
Product has been added to your cart