CTI 2500-ADP1 Analogue Wiring Adapter
2500-ADP1 Analogue Wiring Adapter for Series 500
Description of the 2500-ADP1
The 2500-ADP1 is a wiring adapter that converts 500 Series analogue field www.ge-drive.com wiring from the basic format to the 40-pin connector used on CTI 2500 SeriesTM analogue input/output modules.
The 2500-ADP1 is a wiring adapter that converts the analogue field wiring of the 500 Series from the basic format to the 40-pin connector used on CTI 2500 SeriesTM analogue I/O modules.
Converts analogue field wiring from basic format to the 40-pin connector used on the CTI 2500 SeriesTM analogue I/O modules.
This allows for quick upgrades of existing 500 Series systems to the newer, more suitable 2500 SeriesTM.
Features
The 2500-ADP1 cable allows for the following conversions
field wiring:
– 500-5037A 8-channel analogue input connector to CTI 2558 8-channel analogue input 40F connector.
– 500-5047A 8-channel analogue output connector to CTI 2562 8-channel analogue output 40F connector.
Instructions
Method A – Installing a New Module into an Existing 500 Series I/O Adapter
Chassis
1. Disconnect power to the Series 500 chassis
2. Remove the 500-5037A/47A to be upgraded.
3. Install the 2500-IADP into the slot where the 500 module was removed.
4. Configure the 2558/2562 to match the 500 module to be replaced .
5. Install the 2558/2562 into the 2500-IADP .
6. Connect the edge card connector of the 2500-ADP1 to the existing 5037A / 5047A field wiring connector.
(The screen label on the 2500-ADP1 indicates a 5037A / 5047A field wiring connector).
Connect the edge card connector of the 2500-ADP1 to the existing 5037A / 5047A field wiring connector.
(The screen label on the edge card connector shows pin 1 and pin A.)
7. Remove any 250 ohm resistors that may be installed in the 5037A / 5047A field wiring connector. 2558 / 2562 do not require these resistors.
8. Connect the 40F connector to the 2558/2562.
9. Restore power to the rack.
Method B – Installing a New Module into a New 2500 SeriesTM Base
1. Disconnect power to the 500 Series chassis.
2. Remove the 500-5037A/47A to be upgraded.
3. Configure the 2558/2562 to match the 500 module to be replaced.
4. Install the 2558/2562 into the 2500 SeriesTM base.
5. Connect the edge card connector of the 2500-ADP1 to the existing 5037A / 5047A field wiring connector (The screen label on the edge card connector shows pin 1 and pin A.)
6. remove any 250 ohm resistors that may be installed in the 5037A / 5047A field wiring connector. 2558 / 2562 do not require these resistors.
7. Connect the 40F connector to the 2558 / 2562.
8. Restore power to the rack.